Indukta

Sg 112M-4/2

add to notebook



basic information

IEC 60034-1;PN-EN 60034-
insulation class F
type of duty S!
degree of protection IP 55
cooling system IC 411
frame size 112

exploitation parameters

rated output [kW] 3.3/4.5
synchronous speed [rpm] 1500/3000
frequency [Hz] 50
rated voltage 1 [V] 400
current at rated voltage 1 [A] 6.7
breakdown torque [Nm] 59
locked rotor torque [Nm] 48.31
winding connection D
locked rotor current at rated voltage 1 [A] 46.2
breakdown torque/rated torque 2.7
locked rotor current/rated current 6.9
locked rotor torque/rated troque 2.2
star/delta start nie/no
efficiency (3/4 load) [%] 84.3
efficiency (1/2 load) [%] 83
efficiency (1/4 load) [%] 75.8
number of poles 4/2
rated torque [Nm] 21.96
rated output [HP] 4.50/6.2
efficiency (full load) [%] 83.3
efficiency (5/4 load) [%] 81.5
power factor (1/4 load) 0.44
current at rated voltage 3 [A] 5.4
current at rated voltage 2 [A] 7.1
rated voltage 3 [V] 500
rated voltage 2 [V] 380
power factor (5/4 load) 0.89
power factor (full load) 0.85
power factor (3/4 load) 0.8
power factor (1/2 load) 0.67

technical data

weight (IMB3) [kg] 33
rotor inertia [kgm2] 0.012
climate on request
relative humidity [%] 95
foot aluminium
end shields cast iron
frame aluminium
anticondensation heaters on request
grease fittings on request
thermal protection of windings on request
gland M 25 x 1.5
number of cable outlets 2
number of terminals 6
terminal box rotation yes
position of terminal box top
NDE bearing 6306 2Z
DE bearing 6306 2Z

mounting arrangements

IM 1001 / IM B3 Sg_112.pdf
IM 1051 / IM B6 Sg_112.pdf
IM 1061 / IM B7 Sg_112.pdf
IM 1071 / IM B8 Sg_112.pdf
IM 2001 / IM B35 SLg_112.pdf
IM 3001 / IM B5 SKg_112.pdf
IM 1011 / IM V5 Sg_112.pdf
IM 1031 / IM V6 Sg_112.pdf
IM 2011 / IM V15 SLg_112.pdf
IM 2031 / IM V36 available
IM 3011 / IM V1 SKg_112.pdf
IM 3031 / IM V3 SKg_112.pdf

Cantoni MotorBeselInduktaCelmaEmitEma-ElfaFanaFormitNarmodFenes